
4
Operating Instructions and Parts Manual
Shallow Well Model Systems
1. Shut off the power to the pump.
2. Open the faucet nearest the tank and
allow all water to drain from the tank.
3. Measure the tank precharge at the
valve stem using a tire pressure gauge.
4. If necessary, precharge with an air
pump to 28 - 30 psi on 1/2, 3/4 and 1
HP pumps.
5. Slope the horizontal pipes upward
toward the pump to prevent trapping
air. If the horizontal distance
exceeds 25 feet, see Chart 2 for the
recommended pipe size.
Electrical
Risk of electrical
shock. This pump is
designed for indoor installation only.
The voltage of power supply must match
the voltage of the pump. All above
ground well pumps except SWS50BOOST
have dual voltage motors preset at the
factory to 115 volts. The motors can be
converted to 230 volts by turning the
voltage selector to the desired voltage
(See Figure 7). Use a needle nose pliers
to pull the selector out approximately
1/4”, rotate and then reinsert in correct
position.
Select the proper size wire and
fuse (Chart 3). Time delay fuses are
recommended over standard fuses for
motor circuit protection. All pump
motors have built-in automatic overload
protection that will prevent damage to
the motor due to overheating.
Do not connect to
electric power supply
until unit is permanently grounded.
Connect ground wire to approved
ground then connect terminal provided.
A metal underground water pipe or well
casing at least 10 feet long makes the
best ground electrode. If plastic pipe or
insulated fi ttings are used, run a wire
directly to the metal well casing or use
a ground electrode furnished by the
power company.
There is only one proper ground
terminal on the unit. The terminal(s) is
located under the pressure switch cover,
is painted green and is identifi ed as
GRD. The ground connection must be
made at this terminal (Figure 8). The
ground conductor must not be smaller
than the circuit conductors supplying the
motor.
Disconnect power
and release all
pressure from the system before
attempting to install, service, relocate or
perform any maintenance.
Operation
PRIMING THE SHALLOW WELL PUMP
To prevent damage
to the pump, do not
start motor until pump has been fi lled
with water.
1. Remove prime plug (Figure 4 or 5).
2. Fill pump and piping completely full
of water.
3. Replace the prime plug.
4. Open a faucet to vent the system.
5. Start the motor. Water will pump in
a few minutes. If pump fails to prime
in 5 minutes, stop motor and refill
pump with water. Priming time is
proportional to the amount of air in
inlet pipe.
6. Let the system operate for several
minutes to flush all pipes.
7. Close faucet and allow pump to build
pressure in tank. When the pressure
reaches the cut-out setting, the
motor will stop.
The system is now in operation and will
automatically cycle on demand.
Maintenance
Disconnect power
and release all
pressure from the system before
attempting to install, service, relocate
or perform any maintenance. Lock the
power disconnect in the open position.
Tag the power disconnect to prevent
unexpected application of power.
Protect the pump
from freezing during
winter conditions.
DRAINING THE PUMP
Drain openings are provided on all
models. To drain the pump:
1. Remove drain plug and prime plug to
vent the system.
2. Drain all piping to a point below the
freeze line.
DRAINING THE TANK
Conventional tanks can be drained by
opening an outlet at the lowest point
in the system. Remove plug or the air
volume control to vent the tank.
Precharged tanks force virtually all
the water from the tank when system
pressure is released. No draining is
necessary.
RESTARTING PUMP
If the pump has been serviced, drained
or has not been used for some time,
be sure there is water in the pump
housing (volute) and the piping to the
well. There must be water in the pump
housing (volute) at all times when
the pump is running to avoid internal
damage of seal members (Priming the
Shallow Well).
www.waynepumps.com
115 V
230 V
115 V
230 V
Figure 7 - Voltage Selector
L2
3
L1
1
Figure 8 - Electrical Connections
Line
Motor
Ground
Screw
CHART 3 - RECOMMENDED FUSE & WIRING DATA - 60 HZ MOTORS
HP VOLT
Distance in Feet
From Meter to Motor
0 51 101 201
to to to to
50 100 200 300
Wire Size
1/2
115 15 14 14 10
230 10 14 14 14
3/4
115 15 14 14 8
230 10 14 14 14
1
115 20 12 12 8
230 10 14 14 14
Installation (Continued)
29 Sp
Manuel de Instrucciones y Lista de Piezas Sistemas de modelos para Pozos Poco Profundos
Guía de Diagnóstico de Averías
PRECAUCIONES ELÉCTRICAS - Antes de realizar el servicio a una bomba, apague siempre el disyuntor de
corriente principal y luego desenchufe la bomba. Asegúrese de no estar parado sobre agua y de estar usando zapatos
con suela protectora aislante. En condiciones de inundación, póngase en contacto con su compañía eléctrica local o un electricista licenciado
califi cado para desconectar el servicio de electricidad antes de quitar la bomba.
Problema Posible(s) Causa(s) Acción a Tomar
La bomba no se enciende
o no funciona a velocidad
máxima
1. Fusible quemado o disyuntor abierto 1. Cambie el fusible quemado o disyuntor de cir-
cuito cerrado Consulte la tabla de cableado para
saber el tamaño adecuado del disyuntor/fusible
2. La CA está apagada 2. Encienda la energía
3. Voltaje incorrecto 3. Bajo voltaje
a. El voltaje debe estar dentro de ± 10% del
voltaje indicado para el motor. Verifi que el
voltaje de entrada. Póngase en contacto con la
compañía eléctrica
b. El voltaje del motor está fi jado a 120 V CA.
El sistema no está diseñado para funcionar
a 240 V.
4. Motor defectuoso 4. Cambie el motor
5. Los componentes internos de la bomba
están obstruidos/gastados/dañados
5. Reemplace las piezas gastadas o toda la bomba.
Limpie las piezas si fuera necesario
La bomba funciona
pero sale muy poca
agua o nada
1. Las válvulas instaladas en el sistema
están restringiendo el fl ujo
1. a. Verifi que las válvulas en la entrada de la bomba
y los lados de descarga del sistema. Asegúrese
de que están completamente abiertas para
permitir el fl ujo hacia y desde la bomba.
b. Deje salir el aire atrapado en la bomba.
(normalmente debido a una válvula cerrada
en la tubería de salida).
2. El fi ltro en línea está restringiendo el
fl ujo
2. Verifi que todos los fi ltros de la línea para asegu-
rarse de que no estén tapados o restringidos
3. Bajo voltaje
3. Ver acción correctiva de bajo voltaje de línea (arriba)
4. Suministro inadecuado de agua a la
bomba de aumento de la presión
4. Verifi que la presión en el lado de la entrada de la
unidad de aumento de la presión para asegurarse de
que la presión positiva se mantenga en la bomba de
aumento de presión en todo momento.
5. Tuberías demasiado pequeñas 5. Cambie las tuberías que son demasiado pequeñas
6. Pérdida en el lado de entrada del
sistema
6. Asegúrese de que las conexiones estén ajustadas.
Repare las fugas según sea necesario
7. Piezas de la bomba o bomba gastadas
o defectuosas
7. Reemplace las piezas gastadas o todo el impulsor
tapado. Limpie las piezas si fuera necesario
8. Succiona a una altura demasiado alta 8. La bomba debe ponerse en funcionamiento sólo
bajo succión inundada. Vea la acción correctiva
4 más arriba.
9. La bomba no está cebada 9. Cebe la bomba. Asegúrese de que las conexiones
de las tuberías de entrada están ajustadas y que
la bomba y las tuberías estén llenas de agua.
Ruido excesivo mientras
se bombea
1. La bomba no está asegurada a una
base fi rme
1. Asegure de forma correcta
2. No soporta las tuberías 2. Haga ajustes
3. Línea de entrada restringida 3. Limpie, corrija o elimine las restricciones
4. Cavitación (bombeo de burbujas) 4. Aumente el tamaño de la tubería de entrada
5. Los rodamientos del motor están gastados 5. Cambie el motor
La bomba pierde 1. Sello mecánico gastado (gotea en el eje) 1. Cambie el sello del eje (giratorio)
2. Sellos de anillo en O dañados 2. Cambie la junta cuadrada de goma del anillo
Comentários a estes Manuais