A SCOTT FETZER COMPANY801 GLASGOW AVE.FORT WAYNE, IN 46803US PATENT NO. 4,388,064Publication Date 6/11/07PART NO. 62484-001BMODELSHSG200HSG400GAS BURN
PAGE 9SECTION IIIOPERATION AND TROUBLESHOOTINGSEQUENCE OF OPERATION - HSG SERIES POWER GASCONVERSION BURNER UTILIZING HONEYWELL S89FGAS PRIMARY P/N 62
PAGE 10SEQUENCE OF OPERATION - HSG SERIESPOWER GAS CONVERSION BURNER UTILIZINGHONEYWELL S89E GAS PRIMARY P/N 62758-002 W/ EXTERNAL30 SECOND PREPURGE T
PAGE 11FLAME SENSINGThe Honeywell S89 series primary ignition controlsutilize the flame current rectification principal for mainburner flame sensing.T
PAGE 12
PAGE 13
PAGE 14
PAGE 15SECTION IVSERVICECaution: Make sure the main manual, combinationvalves and main power switch are turnedoff before opening burner or removing an
PAGE 16PART NUMBER DIM “A”21664HSG200 2 1/16”5 1/4 O.D. (52.3875mm)(133.35mm)21642HSG400 2 3/16”5 1/2 O.D. (55.5625mm)(139.7mm) DRAWER ASSEMBLYFigure
PAGE 17PARTS LIST - MODEL HSG 200/400 SEE FIG. 15 & FIG. 17ItemPart No. Description1. 100934-001 Burner Housing2. 62576-003 Air Tube - HSG200 6&qu
PAGE 18
SPECIFICATIONS MODELSHSG200, HSG400 NATURAL OR PROPANE GASNOTE: Dimensions in ( ) are informational only. English values take priority.HSG200Maximum
PAGE 19TECHNICAL INFORMATION“Troubleshooting Guide”NUISANCE LOCKOUTS/FLAME SENSING PROBLEMS - HSG200 & HSG400 GAS BURNERSWayne’s HSG series direct
PAGE 20LIMITED WARRANTIES FOR OIL AND GAS BURNERS, MADE BY WAYNE ANDUSED IN RESIDENTIAL INSTALLATIONSWAYNE COMBUSTION SYSTEMS (“WAYNE”) warrantsto tho
PAGE 21CONSUMER INSTRUCTIONSMAINTENANCE: Keep the area around the burner clear and free of com-bustible materials, gasoline or other flammable liquids
PAGE 22Notes
PAGE 2SECTION IINSTALLATIONA. GENERALThe Wayne HSG200 and HSG400 power gasconversion burners are adaptable to most types ofcentral heating plants prev
Pitch the horizontal run of the flue pipe upward 1/4 inch(6.35mm) per foot (.305m) or more. Run directly to thechimney, fasten joints securely and su
E. COMBUSTION CHAMBERA combustion chamber is normally required toprotect non-heat transfer surfaces, and to provide aradiant bed for rapid heat transf
PAGE 5G. ELECTRICALThe installation must be wired and GROUNDED inaccordance with local codes or in their absence,with the National Electric Code ANSI/
PAGE 6I. COMBINATION GAS VALVEThe 24 VAC combination gas valve serves three (3)functions: (1) manual gas shut-off, (2) main gasflame pressure regulat
PAGE 71. NOTE: Read the applicable sequence ofburner/primary gas control operation inSection 3 Operation and Troubleshootingbefore proceeding.2. Depr
PAGE 8D. The flue gas temperature should be between325˚F (162.78˚C) and 550˚F (287.78˚C)fordomestic gas conversion burners. Higher fluegas temperatur